Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F2 Solution: MULTIPLE SOLUTIONS Cause: INDOOR EVAPORATOR TEMPERATURE SENSOR IS OPEN/SHORT CIRCUITED Remarks: DESCRIPTION:*AC UNIT IN COOLING/DRY MODE: THE INDOOR FAN WILL CONTINUE TO OPERATE WHILE THE COMPRESSOR AND OUTDOOR FAN STOP OPERATION.*AC UNIT IN HEATING MODE: COMPLETE UNIT STOPS OPERATION.REPAIR:1) POOR...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE HC Solution: MULTIPLE SOLUTIONS Cause: PFC PROTECTION Remarks: DESCRIPTION:*AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR STOPS OPERATING WHILE THE INDOOR FAN WILL CONTINUE TO OPERATE. *AC UNIT IN HEATING MODE: THE COMPLETE UNIT STOPS OPERATION.REPAIR:1) SUDDEN CHANGE OF SUPPLY VOLTAGE OF ELECTRIC...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F3 Solution: MULTIPLE SOLUTIONS Cause: OUTDOOR AMBIENT TEMPERATURE SENSOR IS OPEN/SHORT CIRCUITED Remarks: DESCRIPTION:*AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR AND OUTDOOR FAN STOP OPERATING WHILE THE INDOOR FAN WILL CONTINUE TO OPERATE. *AC UNIT IN HEATING MODE: COMPLETE UNIT STOPS OPERATION.REPAIR:1)...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F4 Solution: MULTIPLE SOLUTIONS Cause: OUTDOOR CONDENSER TEMPERATURE SENSOR IS OPEN/SHORT CIRCUITED Remarks: DESCRIPTION:*AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR AND OUTDOOR FAN STOP OPERATING WHILE THE INDOOR FAN WILL CONTINUE TO OPERATE. *AC UNIT IN HEATING MODE: AFTER OPERATING FOR 3...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F5 Solution: MULTIPLE SOLUTIONS Cause: OUTDOOR DISCHARGE TEMPERATURE SENSOR IS OPEN/SHORT CIRCUITED Remarks: DESCRIPTION:COMPLETE UNIT STOPS OPERATION.REPAIR:1) POOR CONTACT/CONNECTION OF INDOOR TEMPERATURE SENSOR (LOOSE):SOLUTION 1) CHECK IF THE SENSOR WIRE PLUG IS LOOSE FROM THE PCB OR NOT. IF YES, INSERT THE...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F6 Solution: MULTIPLE SOLUTIONS Cause: LIMITED/DECREASED FREQUENCY DUE TO OVERLOAD Remarks: DESCRIPTION:ALL SYSTEMS OPERATE NORMALLY, WHILE THE OPERATION FREQUENCY FOR THE COMPRESSOR IS DECREASED.REPAIR:1) THE EVAPORATOR AND CONDENSER ARE DIRTY:SOLUTION 1) CHECK IF THE EVAPORATOR AND CONDENSER ARE DIRTY OR NOT. IF...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F8 Solution: MULTIPLE SOLUTIONS Cause: DECREASED FREQUENCY DUE TO OVERCURRENT Remarks: DESCRIPTION:ALL SYSTEMS OPERATE NORMALLY, WHILE THE OPERATION FREQUENCY FOR THE COMPRESSOR IS DECREASED.REPAIR:1) THE INPUT SUPPLY VOLTAGE IS NOT STABLE:SOLUTION 1) CHECK IF THE SUPPLY VOLTAGE IS TOO LOW. IF YES,...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE F9 Solution: MULTIPLE SOLUTIONS Cause: DECREASED FREQUENCY DUE TO HIGH AIR DISCHARGE Remarks: DESCRIPTION:ALL SYSTEMS OPERATE NORMALLY, WHILE THE OPERATION FREQUENCY FOR THE COMPRESSOR IS DECREASED.REPAIR:1) THE EVAPORATOR AND CONDENSER ARE DIRTY:SOLUTIONS 1) CHECK IF THE EVAPORATOR AND CONDENSER ARE DIRTY OR...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE E2 Solution: MULTIPLE SOLUTIONS Cause: ANTI-FREEZING PROTECTION Remarks: DESCRIPTION:AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR AND OUTDOOR FAN STOP OPERATING WHILE THE INDOOR FAN CONTINUES TO OPERATE.REPAIR:1) POOR AIR RETURN IN INDOOR UNIT:SOLUTION 1) CHECK IF THERE ARE ANY OBSTRUCTIONS AND MAKE...

Symptom: DXG-18, DXH-18, MGC-18 - ERROR CODE E3 Solution: MULTIPLE SOLUTIONS Cause: LOW PRESSURE PROTECTION Remarks: DESCRIPTION:THE COMPLETE UNIT WILL STOP OPERATING.REPAIR:1) THE LPP CONNECTION TERMINAL WIRES OF THE PCB DOESN'T CONNECT WELL WITH THE HIGH PRESSURE SWITCH:SOLUTION 1) CHECK IF THE LPP CONNECTING TERMINAL WIRES OF THE PCB...