Symptom: DXF-19, DXH-19, MGC-19 – ERROR CODE P1

Solution: MULTIPLE SOLUTIONS

Cause: OVER VOLTAGE OR TOO LOW VOLTAGE PROTECTION

Remarks:

DESCRIPTION:

ABNORMAL INCREASES OR DECREASES IN VOLTAGE ARE DETECTED BY CHECKING THE SPECIFIED VOLTAGE DETECTION CIRCUIT.

REPAIR:

1) CHECK THE POWER SUPPLY:

IS IT FUNCTIONING PROPERLY?

NO = TURN OFF THE UNIT
YES = CHECK 2)

2) CHECK THE CONNECTIONS AND WIRES:

ARE THEY FUNCTIONING PROPERLY?

NO = ENSURE PROPER CONNECTIONS OR REPLACE THE WIRES
YES = CHECK 3)

3) TURN ON POWER AND MEASURE THE VOLTAGE BWTWEEN P AND N:

WHILE THE UNIT IS ON STANDBY, IS THE VOLTAGE BETWEEN P AND N AROUND DC 310V, 340V OR 380V? AND WHEN THE UNIT STARTS UP, IS IT IN 220V-400V?

NO = REPLACE THE IPM BOARD
YES = CHECK 4)

4) CHECK THE REACTOR:

IS IT FUNCTIONING PROPERLY?

NO = REPLACE THE OUTDOOR PCB
YES = REPLACE THE REACTOR