72

Symptom: MGC-19,DXH-19, DXF-19 P0

Solution: MULTIPLE SOLUTIONS

Cause: IPM MALFUNCTION OR IGBT OVER-STRONG CURRENT PROTECTION

Remarks:

DESCRIPTION:

WHEN THE VOLTAGE SIGNAL THAT THE IPM SENDS TO THE COMPRESSOR DRIVE CHIP IS ABNORMAL, THE DISPLAY LED SHOWS “P0” AND THE AC TURNS OFF.

***REPAIR OPTION 1 (FOR 9K – 24K):***

1) CHECK THE WIRING BETWEEN PCB AND COMPRESSOR:

DOES AN ERROR EXIST?

YES = ENSURE PROPER CONNECTIONS OR REPLACE THE WIRES AND CONNECTORS
NO = CHECK 2)

2) CHECK THE IPM:

IS IT FUNCTIONING PROPERLY?

NO = REPLACE THE IPM BOARD OR REPLACE THE OUTDOOR PCB
YES = CHECK 3)

3) CHECK THE OUTDOOR FAN AND THE OUTDOOR UNIT VENTILATION:

IS IT FUNCTIONING PROPERLY?

NO = CHECK THE SOLUTION FOR THE FAN SPEED MALFUNCTION (ERROR CODE E3)
YES = CHECK 4)

4) CHECK THE COMPRESSOR RESISTANCE VALUES:

ARE THEY WITHIN ACCEPTABLE PARAMETERS?

NO = REPLACE THE COMPRESSOR
YES = REPLACE THE OUTDOOR PCB

***REPAIR OPTION 2 (FOR 30K – 36K):***

PLEASE CHECK PAGE 106 OF ATTACHMENT FOR DETAILED SERVICE DIAGRAM.