71

Symptom: DXF-19, DXH-19, MGC-19 – ERROR CODE F0

Solution: MULTIPLE SOLUTIONS

Cause: OVERLOAD CURRENT PROTECTION

Remarks:

DESCRIPTION:

AN ABNORMAL CURRENT INCREASE IS DETECTED BY CHECKING THE SPECIFIED CURRENT DETECTION CIRCUIT.

REPAIR:

1) CHECK THE POWER SUPPLY:

IS IT FUNCTIONING PROPERLY?

NO = STOP THE UNIT
YES = CHECK 2)

2) CHECK SYSTEM FOR BLOCKAGES:

DO ANY EXIST?

YES = CLEAR THE BLOCKAGES
NO = CHECK 3)

3) CHECK THE COMPRESSOR RESISTANCE VALUES:

ARE THEY WITHIN ACCEPTABLE PARAMETERS?

NO = REPLACE THE COMPRESSOR
YES = CHECK 4)

4) CHECK THE CONNECTIONS AND WIRES:

ARE THEY PROPERLY CONNECTED?

NO = ENSURE PROPER CONNECTIONS OR REPLACE THE WIRES
YES = CHECK 5)

5) CHECK THE REACTOR:

IS IT FUNCTIONING PROPERLY?

NO = REPLACE THE OUTDOOR PCB
YES = REPLACE THE OUTDOOR UNIT