Symptom: DXF-19, DXH-19, MGC-19 – ERROR CODE EC
Solution: MULTIPLE SOLUTIONS
Cause: REFRIGERANT LEAKAGE DETECTION
Remarks:
DESCRIPTION:
DEFINE THE EVAPORATOR COIL TEMPERATURE. T2 OF THE COMPRESSOR JUST STARTS RUNNING AS TCOOL.
IN THE FIRST 8 MINUTES AFTER THE COMPRESSOR STARTS UP, IF ‘T2 < TCOOL-2 DEGREES CELCIUS' DOES NOT CONTINUE FOR 4 SECONDS AND THE COMPRESSOR RUNNING FREQUENCY IS HIGHER THAN 50HZ AND DOES NOT CONTINUE FOR 3 MINUTES, AND THIS SITUATION HAPPENS 3 TIMES, THE DISPLAY AREA WILL SHOW "EC" AND THE AC UNIT WILL TURN OFF.
REPAIR:
1) TURN POWER OFF, THEN RESTART THE UNIT 2 MINUTES LATER:
DOES A PROBLEM REMAIN?
NO = THE UNIT IS OPERATING NORMALLY
YES = CHECK 2)
2) PUT YOUR HANDS IN FRONT OF THE INDOOR AIR OUTLET:
IS THERE COOL AIR BLOWING OUT FROM THE INDOOR AIR OUTLET?
YES = CHECK THE T2 SENSOR –> IS IT SECURELY ATTACHED? YES = REPLACE THE INDOOR PCB (NO = ATTACH SECURELY)
NO = CHECK 3)
3) CHECK THE SYSTEM FOR LEAKAGES:
ARE ANY LEAKAGES PRESENT?
NO = CHECK THE SYSTEM FOR BLOCKAGES AND CLEAR BLOCKAGES IF PRESENT
YES = REPAIR THE LEAKAGE AND RECHARGE THE REFRIGERANT
REPAIR:
YES = CHECK 2)
NO = CHECK 3)
YES = REPAIR THE LEAKAGE AND RECHARGE THE REFRIGERANT