Symptom: DXF-19, DXH-19, MGC-19 – ERROR CODE E2
Solution: MULTIPLE SOLUTIONS
Cause: ZERO CROSSING SIGNAL DETECTION ERROR
Remarks:
DESCRIPTION:
WHEN PCB DOES NOT RECEIVE ZERO CROSSING SIGNAL FEEDBACK FOR 4 MINUTES OR THE ZERO CROSSING SIGNAL TIME INTERVAL IS ABNORMAL.
REPAIR:
1) CHECK THE CONNECTIONS AND POWER SUPPLY:
IS IT NORMAL?
NO = CORRECT THE CONNECTIONS. TURN ON THE UNIT WHEN THE POWER SUPPLY IS GOOD
YES = INDOOR MAIN PCB IS DEFECTIVE. REPLACE THE INDOOR MAIN PCB
YES = INDOOR MAIN PCB IS DEFECTIVE. REPLACE THE INDOOR MAIN PCB