Symptom: DXG-18, DXH-18, MGC-18 – ERROR CODE EU

Solution: MULTIPLE SOLUTIONS

Cause: LIMITED/DECREASED FREQUENCY DUE TO HIGH TEMPERATURE OF MODULE

Remarks:

DESCRIPTION:

ALL SYSTEMS OPERATE NORMALLY, WHILE THE OPERATION FREQUENCY FOR THE COMPRESSOR IS DECREASED.

REPAIR:

1) THE WIRE CONNECTION OF THE RADIOTOR IS NOT OK (LOOSE):

SOLUTION 1) CHECK IF THE RADIATOR OF THE PCB IS WELL INSTALLED OR NOT. IF NOT, PLEASE ADJUST IT

2) THE SILICONE GREASE IS NOT SUFFICIENT:

SOLUTION 2) CHECK IF THE SILICONE GREASE IS DRY OR NOT. IF YES, PLEASE ADD EXTRA SILICONE GREASE

3) THE PCB IS MALFUNCTIONING:

SOLUTION 3) REPLACE IT WITH A NEW CORRESPONDING PCB OF OUTDOOR UNIT