Symptom: DXG-18, DXH-18, MGC-18 – ERROR CODE HC

Solution: MULTIPLE SOLUTIONS

Cause: PFC PROTECTION

Remarks:

DESCRIPTION:

*AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR STOPS OPERATING WHILE THE INDOOR FAN WILL CONTINUE TO OPERATE.

*AC UNIT IN HEATING MODE: THE COMPLETE UNIT STOPS OPERATION.

REPAIR:

1) SUDDEN CHANGE OF SUPPLY VOLTAGE OF ELECTRIC NET:

SOLUTION 1) CHECK IF THE SUPPLY VOLTAGE IS NOT STABLE. PLEASE ADD A VOLTAGE REGULATOR. ALSO CHECK THE QUALITY OF POWER GRID

2) SHORT CIRCUIT OF ELECTRIC REACTOR OF PFC INDUCTANCE:

SOLUTION 2) REPLACE WITH A NEW CORRESPONDING PCB (SINGLE PCB)

3) THE PCB IS MALFUNCTIONING

SOLUTION 3) REPLACE WITH A NEW CORRESPONDING PFC MODULE (MULTIPLE PCBS)

4) THE REACTOR IS MALFUNCTIONING:

SOLUTION 4) CHECK THE WIRING. IF NEEDED, REPLACE WITH A NEW CORRESPONDING REACTOR

5) THE INDUCTION IS BROKEN:

SOLUTION 5) REPLACE WITH A NEW CORRESPONDING INDUCTION

6) CHECK THE INDOOR AND OUTDOOR HEAT EXCHANGER:

SOLUTION 6) CHECK IF THE INDOOR AND OUTDOOR EXCHANGER IS TOO DIRTY, AND IF THE AIR INLET/OUTLET IS BLOCKED OR NOT