19 Nov 43
Symptom: DXG-18, DXH-18, MGC-18 – ERROR CODE H5
Solution: MULTIPLE SOLUTIONS
Cause: IPM PROTECTION
Remarks:
DESCRIPTION:
*AC UNIT IN COOLING/DRY MODE: THE COMPRESSOR STOPS OPERATING WHILE THE INDOOR FAN WILL CONTINUE TO OPERATE.
*AC UNIT IN HEATING MODE: THE COMPLETE UNIT STOPS OPERATION.
REPAIR:
1) THE WIRING OF THE COMPRESSOR IS NOT OK:
SOLUTION 1) CHECK IF THE WIRING OF THE COMPRESSOR IS CONNECTED PROPERLY, AND CHECK IF THERE IS A MISMATCH BETWEEN THE ELECTRIC BOX AND COMPRESSOR
2) SOMEONE TURNS OFF THE UNIT AND THEN TURNS THE UNIT BACK ON BEFORE THE COMPRESSOR STOPPED FOR 3 MINUTES:
SOLUTION 2) CHECK IF THE STOP DURATION OF THE COMPRESSOR IS LONGER THAN 3 MINUTES
3) LOW VOLTAGE:
SOLUTION 3) CHECK IF THE VOLTAGE IS TOO LOW. IF YES, PLEASE ADJUST IT
4) NORMAL OVERLOAD PROTECTION:
SOLUTION 4) CHECK IF LOADING IS TOO HEAVY. IF YES, IT IS THE NORMAL OVERLOAD PROTECTION
5) SYSTEM IS NOT OK:
SOLUTION 5) CHECK IF THERE IS EXCESSIVE REFRIGERANT, IF THE PIPELINE IS BLOCKED OR IF THE EVAPORATOR OR CONDENSER IS DIRTY
6) DEFECT OF THE OUTDOOR CONTROLLER:
SOLUTION 6) CHECK IF THE OUTDOOR PCB HAS A DEFECT. IF YES, PLEASE REPLACE IT WITH A CORRESPONDING PART
7) DEFECT OF THE COMPRESSOR:
SOLUTION 7) CHECK IF THE COMPRESSOR IS DAMAGED. IF YES, PLEASE REPLACE IT WITH A CORRESPONDING PART
8) INDOOR AND OUTDOOR FANS ARE RUNNING ABNORMALLY:
SOLUTION 8) CHECK IF THE INDOOR AND OUTDOOR FANS ARE RUNNING NORMALLY
9) SYSTEM PRESSURE IS TOO HIGH:
SOLUTION 9) CHECK IF THE SYSTEM PRESSURE IS TOO HIGH. IF YES, PLEASE ADJUST IT
SOLUTION 2) CHECK IF THE STOP DURATION OF THE COMPRESSOR IS LONGER THAN 3 MINUTES