34

Symptom: DXG-18, DXH-18, MGC-18 – ERROR CODE F8

Solution: MULTIPLE SOLUTIONS

Cause: DECREASED FREQUENCY DUE TO OVERCURRENT

Remarks:

DESCRIPTION:

ALL SYSTEMS OPERATE NORMALLY, WHILE THE OPERATION FREQUENCY FOR THE COMPRESSOR IS DECREASED.

REPAIR:

1) THE INPUT SUPPLY VOLTAGE IS NOT STABLE:

SOLUTION 1) CHECK IF THE SUPPLY VOLTAGE IS TOO LOW. IF YES, PLEASE ADJUST IT

2) THE EVAPORATOR AND CONDENSER ARE DIRTY:

SOLUTIONS 2) CHECK IF THE EVAPORATOR AND CONDENSER ARE DIRTY OR NOT. IF YES, PLEASE CLEAN IT

3) THE SYSTEM PRESSURE IS ABNORMAL OR THE REFRIGERANT IS EXCESSIVE:

SOLUTION 3) CHECK IF THE SYSTEM PRESSURE IS NORMAL OR NOT, AND CHECK THE REFRIGERANT LEVEL. IF YES, PLEASE ADJUST IT

4) THE OUTDOOR TEMPERATURE SENSOR IS BROKEN:

SOLUTION 4) CHECK IF THE TEMPERATURE SENSOR OF OUTDOOR UNIT IS OK OR NOT. IF THE SENSOR IS BROKEN, PLEASE REPLACE IT

5) THE OUTDOOR PCB IS BROKEN:

SOLUTION 5) REPLACE WITH A NEW CORRESPONDING OUTDOOR UNIT PCB

6) THE COMPRESSOR IS BROKEN:

SOLUTION 6) REPLACE WITH A NEW CORRESPONDING COMPRESSOR